NEC 240.4(D): The Small-Conductor Rule on the Electrician Exam

You can do a derating problem perfectly and still miss the question. The reason is usually 240.4(D), the small-conductor rule. It caps the overcurrent protection on small conductors no matter what the ampacity table says. It shows up on journeyman and master exams constantly, because it is easy to forget at the end of a long calculation.

Study aid only, not legal or design advice. Confirm every value in the edition your state has adopted and in your own code book.

What 240.4(D) says, in plain terms

For the small sizes, the overcurrent protective device cannot exceed a set value, even if Table 310.16 shows a higher ampacity. The values most people need for the exam:

ConductorMax overcurrent protection
18 AWG copper7 A (with conditions)
16 AWG copper10 A (with conditions)
14 AWG copper15 A
12 AWG aluminum / copper-clad aluminum15 A
12 AWG copper20 A
10 AWG aluminum / copper-clad aluminum25 A
10 AWG copper30 A

The 18 and 16 AWG allowances come with conditions (continuous load limits, specific listed conductor or cable types, and specific overcurrent devices). Read the list items in your code book. Newer editions also expanded where 16 AWG can be used, so check your edition.

Why the 90°C column fools people

Table 310.16 lists 14 AWG THHN copper at 25 A in the 90°C column. 12 AWG is 30 A and 10 AWG is 40 A. Those numbers are real, and you are allowed to use the 90°C column as the starting point for derating. But 240.4(D) still limits the breaker: 15, 20 and 30 A. A typical exam question gives you a 12 AWG THHN with a derating factor that leaves it at, say, 24 A, then asks for the maximum breaker. The answer is 20 A, not 25 A.

The order of operations

  1. Start with the ampacity from Table 310.16 (90°C column if the insulation allows it and you are derating).
  2. Apply corrections: ambient temperature correction and the adjustment for more than three current-carrying conductors.
  3. Check terminations under 110.14(C). Most equipment is rated 60°C or 75°C, so the final usable ampacity cannot exceed that column.
  4. Apply 240.4(D) last for the small sizes. This is the cap.
  5. Pick the overcurrent device at or below the result, using 240.4(B) only where it applies (it does not override 240.4(D) for the small sizes).

Worked example

Six current-carrying 12 AWG THHN copper conductors in one conduit, 30°C ambient. What is the maximum overcurrent protection?

Notice that three different rules land on or near 20 A. Exam writers like that, because every shortcut gives a slightly different wrong answer: 24 A, 25 A, or 30 A.

Where 240.4(D) does not apply

240.4(D) has a short list of exceptions pointed to in 240.4(E) and 240.4(G). Motor circuits (Article 430), air-conditioning and refrigeration equipment (Article 440), fire alarm, Class 1 remote-control, and some specific equipment have their own protection rules. A motor branch circuit on 14 AWG copper can be protected by a larger breaker sized under Article 430 because the motor overload protection handles the overload, and the breaker only handles short circuit and ground fault.

The exam trap here runs the other way: a question about a motor or an AC unit with a nameplate maximum overcurrent rating, where applying 240.4(D) gives you the wrong (too small) answer. Read the load type before you reach for the cap.

Exam traps to watch for

How to tab it

Put a tab on 240.4 and highlight the (D) list. Write "430 / 440 exempt, see (G)" in the margin. When you finish any ampacity problem, glance at the tab before you circle an answer. That habit alone picks up points.

Related guides

Want the whole system? Get How to Navigate the NEC Like a Pro for $39 → The lookup method, 2026 crosswalk, drills and tab-and-mark system in one short PDF.

Learn to Navigate the NEC (2026 NEC edition, 28 pages, PDF). The lookup method, a crosswalk for moved articles, drills, marking system and Massachusetts notes. Written by Tim Hodnicki, Easthampton, MA electrical contractor.

Get the guide for $39   See what's inside

More guides: How to navigate the NEC fast · 2026 NEC changes for exam takers · Massachusetts exam: 527 CMR and the NEC · How to tab and mark your NEC · 30-day journeyman study plan · Box fill calculations (314.16) · Conductor ampacity and derating · Grounding conductor sizing (250.66 vs 250.122) · Voltage drop calculations · Article 120 load calculations (2026 NEC) · 240.4(D) small-conductor rule · NEC exam questions answered