Conductor Ampacity on the Exam: Table 310.16, Terminations and Derating

Ampacity questions trip people up because there are three or four rules stacked on top of each other, and the table alone won't give you the answer. Here's the order I work them in, every time.

References follow the NEC's Article 310, 110.14(C) and 240.4(D) as they've read for the last few editions. Confirm the numbers against the edition your exam uses.

1. Start with Table 310.16

Table 310.16 covers up to three current-carrying conductors in a raceway, cable or earth, at a 30°C (86°F) ambient. Find the size and material (copper or aluminum), then pick the column that matches the insulation's temperature rating: 60°C, 75°C or 90°C.

2. Check the terminations (110.14(C))

A conductor is only as good as the lug it lands on. For circuits rated 100 amps or less, or conductors 14 through 1 AWG, you use the 60°C column unless the equipment is listed and marked for higher. Over 100 amps, or larger than 1 AWG, use 75°C unless marked otherwise. Most equipment today is marked 60/75°C, so on the job 75°C is common, but read what the question tells you about the equipment.

The 90°C column is still useful. You can start derating from the 90°C value for THHN, as long as the final answer doesn't exceed what the terminations allow.

3. Apply corrections and adjustments (310.15)

Current-carrying conductorsPercent of table value
4–680%
7–970%
10–2050%
21–3045%
31–4040%
41 and above35%

Equipment grounding conductors don't count. A neutral that carries only the unbalanced current of a multiwire circuit usually doesn't count either, but read 310.15(E) for when it does.

4. Don't forget the small-conductor rule (240.4(D))

Whatever the table says, copper overcurrent protection is capped at 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG, unless a specific exception applies.

Worked example

Eight current-carrying 12 AWG THHN copper conductors in one conduit, 30°C ambient, 75°C terminations.

Answer: the conductors are good for 21 A, protected at 20 A.

Common traps

Related: box fill calculations and sizing grounding and bonding conductors.

Get the full lookup method, drills and marking system for $39 →

Learn to Navigate the NEC (2026 NEC edition, 28 pages, PDF). The lookup method, a crosswalk for moved articles, drills, marking system and Massachusetts notes. Written by Tim Hodnicki, Easthampton, MA electrical contractor.

Get the guide for $39   See what's inside

More guides: How to navigate the NEC · 2026 NEC changes for exam takers · Massachusetts exam: 527 CMR and the NEC · How to tab and mark your NEC · 30-day journeyman study plan · Box fill calculations (314.16) · Conductor ampacity and derating · Grounding conductor sizing (250.66 vs 250.122) · Voltage drop calculations