Box Fill Calculations for the Electrician Exam (NEC 314.16)

Box fill shows up on almost every journeyman and master exam, and on the job it's the difference between a clean install and a box you can't close. The math is simple once you count the right things. Most wrong answers come from counting something twice or forgetting something that counts.

Section and table numbers here follow NEC 314.16 as it has read for the last few editions. Always confirm against the edition your exam or your inspector uses. In Massachusetts that means the NEC as amended by 527 CMR 12.00.

Step 1: Find the box volume

For standard metal boxes, use the volume in Table 314.16(A). For boxes not in the table (plastic boxes and many device boxes), use the volume marked on the box. Add the volume of plaster rings, extension rings and domed covers if they're marked with a volume.

Step 2: Count the allowances

ItemCounts as
Each conductor that starts outside the box and ends or splices inside1 allowance, sized by that conductor
Each conductor that passes through without a splice1 allowance
Conductors that start and end inside the box (pigtails)0
Internal cable clamps (one or more)1 allowance, sized by the largest conductor in the box
Each luminaire stud or hickey1 allowance, sized by the largest conductor
Each device yoke or strap (receptacle, switch)2 allowances, sized by the largest conductor connected to that device
All equipment grounding conductors1 allowance for up to four, sized by the largest EGC, plus 1/4 allowance for each one beyond four

A fixture's own wires that are 16 AWG or smaller (up to four of them, plus the fixture ground) don't count when a domed canopy covers the box, per the exception in 314.16(B)(1).

Step 3: Multiply by the volume per conductor

Table 314.16(B) gives the volume each conductor needs:

Size (AWG)Cubic inches each
181.50
161.75
142.00
122.25
102.50
83.00
65.00

Worked example

A single-gang box has one duplex receptacle, two 12/2 NM cables (with ground) coming in, and internal cable clamps.

Total: 8 allowances × 2.25 cu in = 18.0 cubic inches. A box marked 18 cu in or more works. A smaller one doesn't.

Common traps

For the lookup side, see how to navigate the NEC fast. Want to drill this kind of question under the clock? The 30-day study plan builds it in.

Get the full lookup method, drills and marking system for $39 →

Learn to Navigate the NEC (2026 NEC edition, 28 pages, PDF). The lookup method, a crosswalk for moved articles, drills, marking system and Massachusetts notes. Written by Tim Hodnicki, Easthampton, MA electrical contractor.

Get the guide for $39   See what's inside

More guides: How to navigate the NEC · 2026 NEC changes for exam takers · Massachusetts exam: 527 CMR and the NEC · How to tab and mark your NEC · 30-day journeyman study plan · Box fill calculations (314.16) · Conductor ampacity and derating · Grounding conductor sizing (250.66 vs 250.122) · Voltage drop calculations